this walk-in freezer had a compressor replaced, then they began tripping the main breaker when they tried to operate the new compressor. all components were wired properly, diagnosing a bad 3 phase compressor contactor.
Watch video Load phase loss, phase monitor lock out. online, duration hours minute second in high quality that is uploaded to the channel Everything HVACR 15 June 2024. Share the link to the video on social media so that your subscribers and friends will also watch this video. This video clip has been viewed 5,783 times and liked it 111 visitors.